Outdoor SF6 Vacuum Circuit Breaker(60~80USD/PC)

Description

ZW20 12F series outdoor high-voltage AC demarcation vacuum circuit breakers are high-voltage outdoor switchgear with rated voltage of 12KV and three-phase AC 50H z. They are mainly used to open and close the load current, overload current and short circuit of rural power grids, urban power grids and small power systems. Current. The overall structure of the product is a three-phase common box type, and the three-phase vacuum interrupter is placed in a metal box, with reliable voltage transformation performance and high insulation strength.

Contact by Email: sales@zfemcl.com

Description

Features of outdoor sf6 vacuum circuit breaker

Outdoor sf6 vacuum circuit breaker adopts vacuum interrupter for arc extinguishing, it uses composite insulation structure of epoxy solid and air insulation, which avoids damage to the environment caused by using SF6 gas.
Outdoor sf6 vcb could be remote controlled and automatically protected which also named as Overcurrent fault isolation function: the device has overcurrent protection function, when overcurrent fault occurs at the switch load side, the switch starts instantaneous quick-break function to trip the switch, in order to isolate the overcurrent fault from the main line, thus it does not affect normal operation of the main line;

 

Data Sheet

Item Unit Data
Rated voltage KV 12
Rated current A 630
Rated frequency HZ 50
Rated short-time withstand current (RMS) KA/4S 20
Rated peak withstand current KA 50
Rated short-circuit making current (peak) KA 50
Rated short-circuit breaking current KA 20
Rated short-circuit breaking current times Times 30
Rated active load breaking current A 630
Rated breaking capacity of no-load transformer KVA 1250
Rated closed loop breaking current of distribution line A 630
Rated cable charging breaking current A 25
1min Power frequency withstand voltage Wet test, to-ground KV 30
Dry test phase-to-phase, to-ground,isolating distance KV 42
Lightning impulse withstand voltage (peak) Isolating distance KV 85
Phase-to-phase and to-ground KV 75
IP code IP67
External insulation creepage distance > 30mm/Kv
Rated operating sequence ON-0.3s-ON/OFF-180s-ON/OFF
Operating times at rated current 10000
Mechanical operating times 10000
Altitude m 2000
Max ambient temperature 40
Min ambient temperature -40
N.W. kg 140