Outdoor high voltage FZW28-12kV Series Load Break Switch(60~80USD/PC)

FZW28-12F series of outdoor demarcation vacuum load and shutoff is suitable for outdoor three-phase AC power distribution system with rated voltage of 12kV and rated frequency of 50Hz, as the function of opening and closing load current and closing short-circuit current. It is suitable for substations, industrial and mining enterprises, urban and rural power grids as protection cities, rural power grid automated power distribution networks, and places with frequent operations. Boundary load switch is composed of FZW28-12 vacuum load switch and controller, which are electrically connected through aviation sockets and outdoor sealed control cables.

Contact by Email: sales@zfemcl.com

分类:

描述

FZW28-12F series of outdoor demarcation vacuum load and shutoff is suitable for outdoor three-phase AC power distribution system with rated voltage of 12kV and rated frequency of 50Hz, as the function of opening and closing load current and closing short-circuit current. It is suitable for substations, industrial and mining enterprises, urban and rural power grids as protection cities, rural power grid automated power distribution networks, and places with frequent operations. Boundary load switch is composed of FZW28-12 vacuum load switch and controller, which are electrically connected through aviation sockets and outdoor sealed control cables. It can reliably judge the milliampere zero-sequence current and phase-to-phase interruption current inside and outside the detection range, and is suitable for power distribution systems with different neutral point grounding methods

Data Sheet

Model
FZW28-12
FZW28-24
Rated voltage
kV
12
24
Rated frequency
Hz
50
50
Rated current
A
630
630
Rated short-time withstand current
kA
20 (4s)
20(4s)
Rated peak withstand current (peak)
kA
50
50
Rated short circuit breaking current
kA
20
20
Mechanical endurance
Ops
10000
10000
Power frequency withstand voltage (1min) (wet)(dry) phase to phase/isolating distance
kV
42/48
65/79
Lighting impulse withstand voltage (peak) (wet)(dry) phase to phase/isolating distance
kV
75/85
125/145

Model Meaning

 

Installation Dimensions

 

评价

目前还没有评价

成为第一个“Outdoor high voltage FZW28-12kV Series Load Break Switch(60~80USD/PC)” 的评价者